- Why Freeze Damage Is the Most Expensive Winter Failure in a Plastics Plant
- Mapping the Cooling Circuits in a Plastics Plant
- Freeze Risk Assessment by Component
- Glycol-Based Protection: Concentration and Trade-Offs
- Corrosion and Inhibitor Management
- Drainage Strategy for Seasonal Shutdown
- Heat Tracing and Insulation
- Cooling Tower Winter Operation
- Chiller Winter Protection
- Flow and Velocity: The Cheapest Anti-Freeze
- Water Quality Beyond Freezing
- Equipment-Specific Winter Checklist by Machine Type
- Safe Restart After Cold Shutdown
- Requirement to Recommended Winterization Package
- Wanplas Group Equipment and Winterization Support
- Service and Support
- Frequently Asked Questions
- Conclusion
The single most expensive accident a plastics plant suffers in winter is almost never a motor burnout, a screw seizure or a controller failure. It is a freeze-burst. A mold cooling channel splits along the drill line overnight, a plate heat exchanger opens along a gasket lane, a cooling tower coil ruptures in three places, a buried line cracks under the yard, and the plant discovers all of it at seven in the morning when the operator opens the main water valve and floods the workshop. The repair itself is bad enough, but the real loss is the mold that has to be re-drilled or scrapped, the production days that disappear while a replacement exchanger is sourced, and the delivery penalties that follow. Against that, the cost of a properly engineered winterization program is trivial.
This guide treats winter anti-freezing maintenance for plastic machinery cooling water systems as an engineering discipline rather than a seasonal habit. It maps the three water circuits that exist in almost every plastics plant, ranks each component by freeze risk, works through glycol chemistry and concentration selection with the heat transfer penalty spelled out, gives a repeatable drainage and air-purge procedure, and covers heat tracing, cooling tower winter operation, chiller protection, flow strategy, water quality and a machine-by-machine checklist. It closes with a safe cold restart sequence and a requirement-to-solution selection table.
Wanplas, founded in 2017 and established as a brand with partner factories in 2022, operates a network of seven specialized machinery factories with more than 300 employees and equipment exported to over 100 regions. Because the group builds extrusion blow molding machines, twin-screw compounding extruders, PET blow molding machines, injection blow molding machines, recycling washing lines, pipe extrusion lines and sheet and board extrusion lines, its engineers see the same winter failures repeat across every one of those machine families. The recommendations below come from that installed base, not from a generic HVAC manual.
Why Freeze Damage Is the Most Expensive Winter Failure in a Plastics Plant
Freeze damage is uniquely destructive because it is silent, simultaneous and internal. A bearing failure announces itself with noise and heat; a freeze-burst happens at three in the morning in an unmanned workshop and reveals itself only when the system is repressurized. It also tends to occur in many places at once, because the whole plant experiences the same cold night. A plant that loses one mold to freezing has usually lost several other components at the same time and simply has not found them yet.
The physics is straightforward. As water cools below 4 degrees Celsius its density decreases, and at the phase change to ice the volume increases by roughly 9 percent. Because a closed cooling channel is a rigid container, the expanding ice generates hydraulic pressure that can exceed 200 MPa locally. Every metal used in cooling circuits — copper mold channel inserts, brass fittings, stainless plate packs, cast iron pump casings, galvanized steel pipe — yields long before that. The failure signature is characteristic: a longitudinal split following the axis of the passage, or a bulged and cracked casing wall.
The Four Classic Freeze Losses
Mold cooling channels. This is the most expensive single failure. Mold cooling passages are drilled deep into hardened tool steel with baffles, bubblers and conformal circuits that cannot be fully drained by gravity. When water trapped behind a baffle freezes, it splits the channel wall into the cavity area or into a slide pocket. Repair means welding hardened steel, re-machining, re-polishing and re-qualifying the tool, and on precision blow molds or preform molds the tool is often written off.
Plate heat exchangers. Brazed and gasketed plate packs have extremely narrow channels with high surface-to-volume ratio, which is exactly why they freeze first. A plate pack that has frozen usually shows internal cross-leakage between the process side and the tower side, contaminating the clean loop with tower water and its dissolved solids. Detection is often delayed because the unit still passes water.
Cooling tower fill, basin and coils. Open towers left with water in the basin during a hard freeze form an ice mass that deforms the fill packing, cracks the distribution laterals and can overload the tower structure. Closed-circuit towers add the far worse failure mode of a burst coil, which drains the closed loop into the tower basin.
Outdoor pipework, valves and buried lines. Exposed risers, drain legs, instrument tappings, dead branches and shallow-buried yard lines all freeze before the main headers do, because small bore means low thermal mass. Butterfly valve bodies and check valve chambers are frequent casualties, and buried failures are the most expensive to find and excavate.
| Failure type | Typical trigger | Detection difficulty | Repair complexity | Relative loss level |
|---|---|---|---|---|
| Mold cooling channel split | Residual water behind baffles after gravity drain | High — found on refill | Weld, re-machine, re-polish, re-qualify | Very High |
| Plate heat exchanger rupture | Stagnant water in narrow channels, no flow at night | Very High — cross-leak, unit still passes water | Replace plate pack or complete unit | High |
| Cooling tower coil or fill damage | Basin water frozen, fan running into freezing plume | Medium — visible ice, leak on start | Coil replacement, fill re-pack | High |
| Outdoor pipe and valve burst | Small bore, no insulation, no circulation | Low — leaks visibly on refill | Cut and re-weld section, replace valve | Medium |
| Buried yard line crack | Shallow burial above frost line, no drainage fall | Very High — unexplained make-up water | Excavation, replacement, reinstatement | Very High |
| Pump casing and mechanical seal damage | Water left in volute with drain plug closed | Medium — leak or seal failure on start | Casing and seal replacement | Medium |
The economic asymmetry is what makes winterization such an easy decision. Glycol charge, heat tracing, insulation and a documented drainage routine sit at a Low to Medium cost level relative to the plant’s annual maintenance budget. A single mold repair plus the associated downtime sits at Very High. Expressed as an index where a full winterization program for a medium plastics plant equals 100 index points, a single mold cooling channel failure with three days of lost output typically lands between 600 and 1,500 index points, and a buried line excavation in frozen ground can exceed that again.
Mapping the Cooling Circuits in a Plastics Plant
You cannot protect a system you have not mapped. Almost every plastics plant, regardless of whether it runs extrusion blow molding, PET stretch blow molding, twin-screw compounding, pipe extrusion or sheet extrusion, operates three functionally distinct water circuits with very different temperatures, materials and freeze exposures. Treating them as one system is the root cause of most winter failures, because the protection strategy that suits a 32 degree Celsius tower loop is completely wrong for a 7 degree Celsius chilled loop.
Circuit 1: Mold and Product Cooling (Chilled Water)
This is the low-temperature loop, supplied by a chiller and typically running between 5 and 25 degrees Celsius depending on the process. Extrusion blow molding molds run cold to shorten cycle time; PET stretch blow molds run in a controlled band to manage crystallinity and base clearance; preform injection molds run cold with tight tolerance. This circuit usually contains the most expensive and least drainable hardware in the plant, and it is normally indoor. Its danger is not ambient freezing but chiller evaporator freezing and, during a long unheated shutdown, freezing inside molds that sit close to roller shutter doors.
Circuit 2: Machine and Hydraulic Oil Cooling (Tower Water)
This is the medium-temperature loop, typically 30 to 35 degrees Celsius supply, rejecting heat through an open or closed cooling tower. It serves hydraulic oil coolers, gearbox oil coolers, motor and drive cooling, screw feed throat cooling and chiller condensers. It is the circuit most exposed to outdoor conditions because the tower and its risers are on the roof or in the yard. Oil selection and lubrication scheduling for those gearboxes and hydraulic systems is a separate maintenance topic; here the concern is only that the water side of the oil cooler stays liquid and flowing.
Circuit 3: Process-Specific Circuits
These are the circuits engineers forget. They include extruder barrel feed zone cooling jackets, screw core cooling, vacuum calibration tanks on pipe lines, spray cooling baths, chill rolls on sheet and film lines, calibration sleeve cooling, blow pin and neck cooling on blow molding machines, cutting chamber cooling on pelletizing systems, and the numerous small water tanks in a recycling washing line. Individually they are small; collectively they represent the majority of freeze incidents, because each one has small-bore piping, a low-point drain nobody knows about and a dead leg somewhere.
| Parameter | Mold cooling circuit | Machine and oil cooling circuit | Process-specific circuits |
|---|---|---|---|
| Typical supply temperature | 5 to 25 degrees Celsius | 30 to 35 degrees Celsius | 10 to 60 degrees Celsius depending on duty |
| Heat rejection device | Chiller (air-cooled or water-cooled) | Open or closed cooling tower | Shared from circuit 1 or 2, sometimes standalone |
| Loop type | Usually closed, sometimes open tank | Open recirculating | Mixed, frequently open tanks |
| Typical pipe size range | DN25 to DN80 branches, DN100 headers | DN80 to DN200 | DN15 to DN50, many flexible hoses |
| Outdoor exposure | Low (chiller outdoors, distribution indoors) | High (tower, risers, yard mains) | Low to medium (tanks indoors, drains at wall line) |
| Water quality sensitivity | Very high — small passages, tight tolerance | Medium — fouling raises oil temperature | High on chill rolls and calibration tanks |
| Preferred winter strategy | Inhibited glycol plus continuous circulation | Basin heating, bypass control, tower-side glycol on closed towers | Full drainage and air purge on shutdown |
| Consequence of freezing | Very High — mold damage | High — tower and exchanger damage | Medium to High — tank, roll and hose damage |
The mapping exercise itself should produce three deliverables: a marked-up single-line diagram of each circuit with every low point and high point identified, a numbered valve and drain schedule, and a photographic register of outdoor exposures. Plants that keep these three documents current recover from a cold snap in hours; plants that do not spend the first winter morning guessing which valve drains which branch.
Freeze Risk Assessment by Component
Freeze risk is a function of four variables: water temperature, exposure to ambient air, thermal mass, and whether the water is moving. A large indoor header full of 32 degree Celsius circulating water is effectively immune. A DN20 outdoor drain leg full of static water at the same temperature will be solid within a few hours of a hard frost. Ranking components on these four variables produces a protection priority list that directs budget where it actually matters.
The assessment below assumes a plant in a region that experiences sustained sub-zero ambient temperatures, with the understanding that plants in mild winter regions can down-rate the outdoor categories by one level but should not down-rate the shutdown categories at all. Weekend and holiday shutdowns are when most freeze damage happens, because the internal heat load of the machinery disappears and the workshop temperature tracks ambient within a few hours.
| Component | Typical water temperature | Exposure | Freeze risk | Recommended protection |
|---|---|---|---|---|
| Cooling tower basin and fill | 25 to 32 degrees Celsius running | Outdoor | Very High | Basin electric heater, indoor sump conversion, full drain on shutdown |
| Closed-circuit tower coil | 30 to 35 degrees Celsius | Outdoor | Very High | Inhibited glycol in the closed side, bypass flow, fan staging |
| Outdoor riser and yard main | 30 to 35 degrees Celsius | Outdoor | High | Insulation plus self-regulating heat tracing, continuous circulation |
| Shallow buried yard line | 25 to 35 degrees Celsius | Below grade | High | Bury below frost line, fall to a drainable low point, circulation |
| Air-cooled chiller evaporator | 5 to 15 degrees Celsius | Outdoor | Very High | Glycol charge, flow switch interlock, low temperature cut-out, casing heater |
| Plate heat exchanger (free cooling) | 5 to 20 degrees Celsius | Indoor or outdoor plant room | High | Glycol on both sides where applicable, no-flow interlock, drain valves at base |
| Mold cooling channels | 5 to 25 degrees Celsius | Indoor, near shutter doors | High during shutdown | Air purge each circuit, or leave circulation running |
| Manifolds and quick couplings | 5 to 25 degrees Celsius | Indoor | Medium | Drain and purge, disconnect hoses on long shutdowns |
| Extruder barrel feed zone jacket | 15 to 40 degrees Celsius | Indoor | Medium | Drain valve at lowest point, purge, verify no trapped pocket |
| Vacuum calibration tank and spray bath | 12 to 25 degrees Celsius | Indoor | Medium | Full tank drain, pump casing drain, nozzle line purge |
| Chill roll internal passages | 10 to 90 degrees Celsius | Indoor | Medium | Rotary union purge, roll drained through low port |
| Pump casings and volutes | Circuit temperature | Indoor or plant room | Medium to High | Open drain plug, or periodic pump run schedule |
| Instrument tappings and gauge legs | Circuit temperature | Any | High | Isolate and drain, trace where retained in service |
| Fire and make-up water branches | Ambient | Outdoor | Very High | Heat tracing, drainable design, keep in circulation loop |
| Indoor main headers | 25 to 35 degrees Celsius | Indoor heated area | Low | Standard insulation, no special measure |
Two rules simplify the whole exercise. First, anything outdoors and anything smaller than DN25 should be assumed at risk regardless of its nominal temperature. Second, any component that cannot be verified empty by a positive test — air blowing free from the far end, or a drain running dry — must be protected chemically or thermally rather than by drainage, because unverified drainage is the single most common cause of freeze damage in plants that believe they winterized properly.
Glycol-Based Protection: Concentration and Trade-Offs
Glycol is the default chemical answer to freeze risk, and it works reliably — but it is not free performance. Every percentage point of glycol added to a cooling loop lowers the freezing point, lowers the specific heat, raises the viscosity, raises pumping power and reduces the heat transfer coefficient. A plant that adds glycol without recalculating the hydraulics frequently trades a winter freeze problem for a summer capacity problem, and then blames the machine.
Two glycols are used industrially. Ethylene glycol, written as MEG, offers better freeze depression per unit volume, lower viscosity and higher specific heat than propylene glycol, and is the standard choice for closed industrial loops with no food contact risk. Propylene glycol, written as PG, is available in food-safe grades and is the correct choice where the cooling fluid could conceivably contact product or product-contact surfaces — for example in a plant producing food-grade PET bottles or pharmaceutical containers, where a leak from a mold cooling channel into a container-forming zone must not create a toxicity issue.
MEG Versus PG: The Engineering Trade-Off
| Property | Ethylene glycol (MEG) | Propylene glycol (PG) | Practical implication |
|---|---|---|---|
| Freeze depression per unit volume | Higher | Lower — needs roughly 5 to 8 percentage points more for the same protection | PG loops carry more glycol and lose more heat transfer |
| Specific heat at 30 percent volume | Approximately 3.75 to 3.85 kJ per kg per K | Approximately 3.80 to 3.90 kJ per kg per K | Both below water at 4.18; flow must rise to carry the same load |
| Viscosity at 0 degrees Celsius, 30 percent volume | Approximately 3.5 to 4.5 mPa·s | Approximately 6 to 8 mPa·s | PG penalizes pump head and laminar-flow heat transfer more |
| Thermal conductivity | Moderately reduced versus water | Reduced slightly more than MEG | Affects plate exchanger and mold channel performance |
| Toxicity | Toxic if ingested; industrial handling controls required | Low toxicity; food-safe grades available | PG mandatory for food and pharmaceutical contact risk zones |
| Typical duty in a plastics plant | Chiller loops, closed tower coils, outdoor mains | Food-grade PET and pharmaceutical container lines, product-adjacent circuits | Segregate the two; never mix inhibitor packages |
| Relative fluid cost level | Medium | High | Cost difference is minor against a single freeze event |
| Service life before renewal | Typically 3 to 5 years with inhibitor top-up | Typically 3 to 5 years with inhibitor top-up | Both degrade by oxidation, not evaporation |
Concentration Versus Freeze Point and Burst Point
Two temperatures matter, and confusing them is a common and expensive error. The freeze point is where ice crystals begin to form and the fluid turns to slush; flow is already compromised at this point. The burst point is the much lower temperature at which the slush becomes rigid enough to damage the container. Slush at the freeze point will not usually crack a pipe, but it will starve a pump, trip a flow switch and stop production, so system design should target the freeze point with margin, not the burst point.
| MEG concentration (percent by volume) | Freeze point | Burst protection | Heat transfer penalty versus water | Pump head increase | Recommended application |
|---|---|---|---|---|---|
| 20 percent | Approximately minus 8 degrees Celsius | Approximately minus 18 degrees Celsius | 5 to 10 percent | 5 to 8 percent | Mild winter regions, indoor loops with brief exposure |
| 30 percent | Approximately minus 15 degrees Celsius | Approximately minus 30 degrees Celsius | 10 to 15 percent | 10 to 15 percent | General purpose; most temperate plants and outdoor chillers |
| 40 percent | Approximately minus 24 degrees Celsius | Approximately minus 45 degrees Celsius | 15 to 22 percent | 18 to 25 percent | Cold regions, rooftop towers, exposed yard mains |
| 50 percent | Approximately minus 37 degrees Celsius | Approximately minus 60 degrees Celsius | 20 to 30 percent | 28 to 40 percent | Severe cold regions with prolonged sub-zero periods |
| Above 60 percent | Freeze point rises again | Not improved | Above 30 percent | Above 45 percent | Not recommended — inverted curve, excessive viscosity |
Practical Charging Rules
- Set concentration from the lowest recorded ambient temperature at the most exposed point of the circuit, plus a margin of about 5 degrees Celsius. Do not set it from the average winter temperature.
- Pre-mix glycol with treated water before charging. Adding neat glycol to a running loop produces stratified concentration and local pockets that still freeze.
- Use demineralized or softened water for the dilution. Hard water plus glycol accelerates scale formation and consumes inhibitor.
- Never mix MEG and PG, and never mix inhibitor chemistries. Mixed packages can drop out of solution and block small mold channels.
- Re-check concentration with a refractometer after every make-up event. Leaks are replaced with plain water, and a loop that has been topped up three times over a winter may be well below its design protection level.
- Label every charged circuit at the fill point with fluid type, concentration and date. Unlabelled loops get topped up with water by whoever is on shift.
Where a plant genuinely cannot accept the heat transfer penalty — for example a high-speed PET blow molding line where mold cooling directly governs output — the correct answer is not a weaker glycol charge but a split system: glycol only in the outdoor and vulnerable sections, with a plate heat exchanger separating a clean water indoor loop that is kept warm and circulating. This is more capital-intensive but preserves full summer capacity.
Corrosion and Inhibitor Management
Glycol solves freezing and creates corrosion. Uninhibited glycol in a hot, aerated loop oxidizes progressively into organic acids, principally glycolic acid, which drives pH downward. Once pH falls below about 7.0 the solution attacks copper, brass, solder joints and mild steel aggressively, and a system that was charged to prevent a burst pipe ends up with pinholes in the mold cooling channels three years later. This is the most under-managed aspect of glycol systems in plastics plants.
Inhibited glycol products contain a corrosion inhibitor package that is consumed over time by exactly the reactions it prevents. Inhibitor depletion is not visible; the fluid still looks and feels correct and the refractometer still reads the design concentration, because glycol does not evaporate. Only a laboratory or field test kit reveals that the reserve alkalinity has run out. A yearly test before the heating season is the minimum acceptable practice, and semi-annual testing is preferable on loops running above 45 degrees Celsius, since oxidation rate rises sharply with temperature.
The Standard Test Panel
| Test parameter | Target range | Method | Frequency | Action if out of range |
|---|---|---|---|---|
| pH | 8.0 to 9.5 for inhibited glycol loops | Calibrated meter, not paper strips | Quarterly | Below 7.5: test inhibitor reserve, plan fluid renewal |
| Glycol concentration | Design value, tolerance plus or minus 3 percentage points | Handheld refractometer, hydrometer as backup | Monthly in winter, after every make-up | Low: add pre-mixed concentrate, never neat glycol into cold loop |
| Reserve alkalinity | Per fluid supplier specification | Titration test kit | Annually before winter | Depleted: inhibitor top-up or full fluid change |
| Conductivity | Below 1,500 microsiemens per cm on closed loops | Conductivity meter | Quarterly | Rising trend indicates ingress or degradation |
| Chloride | Below 25 mg per litre for stainless plate packs | Ion test kit | Semi-annually | High: identify make-up water source, consider demineralized make-up |
| Total hardness as calcium carbonate | Below 50 mg per litre in closed glycol loops | Titration | Semi-annually | High: switch to softened or demineralized make-up water |
| Iron and copper content | Iron below 3 mg per litre, copper below 0.3 mg per litre | Laboratory analysis | Annually | Rising: active corrosion, investigate immediately |
| Total bacteria count | Below 10,000 CFU per millilitre | Dip slide | Semi-annually, more often on open loops | High: biocide dosing program, clean strainers |
| Visual appearance | Clear, no sediment, no separation | Sample bottle inspection | Every sampling | Cloudy or dark: inhibitor drop-out or degradation |
Material Compatibility Notes
Galvanized steel is the classic incompatibility. Zinc reacts with many glycol inhibitor packages, forming a gelatinous precipitate that blocks strainers and small passages, and this failure mode is particularly damaging in mold cooling circuits where channel diameters may be only 6 to 12 mm. If a plant has galvanized distribution piping and intends to convert to glycol, either the piping must be replaced or a glycol formulation specifically validated for galvanized systems must be used.
Aluminum components — some oil coolers, some chiller evaporator components, some manifold blocks — require an inhibitor package rated for aluminum at the operating temperature. Elastomers matter too: gasketed plate heat exchangers, mechanical seals, hose linings and rotary union seals must be confirmed compatible with the chosen glycol. Ordinary nitrile is generally acceptable with both MEG and PG at these temperatures, but a mixed plant should verify each item rather than assume.
Finally, keep a small stock of pre-mixed fluid at the design concentration. Leaks are inevitable, and the temptation to top up with plain water because the correct fluid is not on site is the single most reliable way to dilute a 40 percent charge down to 25 percent over one season without anyone noticing.
Drainage Strategy for Seasonal Shutdown
Drainage is the cheapest freeze protection and the one most often done badly. Gravity drainage alone never empties a plastics plant cooling system, because the system is full of horizontal runs without fall, U-bends in flexible hoses, baffled mold channels, plate packs with narrow ports, pump volutes below the drain line, and valve bodies with pockets. A drainage program that is not followed by compressed air purging and a positive verification step is not a drainage program; it is a hope.
The Standard Drain-Down Sequence
- Isolate the supply. Close and lock the make-up water valve and the main supply isolation to the circuit being drained. Fit a tag stating the circuit is drained and must not be refilled without authorization.
- De-energize and interlock. Switch off circulation pumps, chillers and tower fans on the affected circuit and isolate electrically. Any pump that starts against an empty suction will destroy its mechanical seal within seconds.
- Open the highest vent first. Break the vacuum before opening low-point drains, otherwise the system will drain partially and then air-lock, leaving trapped water in exactly the wrong places.
- Open all low-point drains. Work from the far end of the circuit back toward the plant room, in sequence, using the numbered drain schedule created during circuit mapping.
- Purge with compressed air at 0.4 to 0.6 MPa. Apply dry compressed air at each branch and hold until air discharges clear and dry from the drain. Never exceed the design pressure of the weakest component, and never use air on a gasketed plate pack above its rated pressure.
- Purge mold cooling circuits individually. Every mold circuit, one at a time, through the actual quick coupling used in production. Baffled and bubbler circuits need longer purge time. Disconnect and drain the hoses separately; a looped hose on the floor holds water indefinitely.
- Empty the cooling tower basin. Open the basin drain fully, sweep out residual water, and check the distribution laterals and the strainer chamber.
- Remove pump casing drain plugs. Every circulation pump, booster pump, spray pump and tank pump. Leave the plug out and place it in a labelled bag attached to the pump.
- Drain tanks, baths and calibration boxes. Vacuum calibration tanks, spray baths, quench tanks, washing line tanks and the associated nozzle headers all hold water below their nominal drain line.
- Record and tag. Sign off each item on the checklist with the operator name and time, and hang a physical tag at each drained machine. Restart authority belongs to whoever holds the completed checklist.
| Drain-down checklist item | Method | Verification | Common failure if skipped |
|---|---|---|---|
| Make-up water isolated and locked | Valve closed, lock and tag fitted | Visual, tag signed | System silently refills overnight and freezes |
| High-point vents opened | Manual vent valves opened | Air audibly entering | Air lock leaves branches full |
| All low-point drains opened | Per numbered drain schedule | Each drain runs then stops | Unknown drain left closed, section stays full |
| Compressed air purge at 0.4 to 0.6 MPa | Dry air through each branch | Clear dry air at outlet for 30 seconds | Residual pockets freeze and split pipe |
| Each mold circuit purged individually | Air through production quick couplings | Dry discharge from each return | Mold channel splits — Very High loss |
| Cooling hoses disconnected and drained | Uncouple, hang vertically | No water on shaking | Hose splits, coupling cracks |
| Plate heat exchanger drained and purged | Base drain plus low-pressure air | Dry at both ports | Plate pack cross-leak — High loss |
| Tower basin emptied and swept | Basin drain plus manual sweep | Basin visibly dry | Ice mass deforms fill and laterals |
| Pump casing plugs removed | Drain plug out, bagged and labelled | Plug visible in bag on pump | Casing cracks, seal destroyed |
| Tanks, baths and calibration boxes emptied | Drain plus residual pump-out | Bottom visibly dry | Tank wall or nozzle header cracks |
| Instrument tappings and gauge legs isolated | Isolate, crack open to drain | No water at test point | Gauge and transmitter destroyed |
| Checklist signed and machine tagged | Written record per machine | Tag hung at operator panel | Machine refilled by mistake before restart approval |
Drainage suits plants with long, planned shutdowns — a two-week holiday, a seasonal product changeover, or a mothballed line. It is the wrong strategy for weekend shutdowns in a plant that must restart on Monday morning, because the labor cost and restart risk repeat every week, and the probability of one missed circuit approaches certainty over a season. For weekly cycling, glycol plus circulation is the correct choice.
Heat Tracing and Insulation
Heat tracing and insulation work as a pair, and neither performs without the other. Insulation alone only slows the rate of heat loss; given a long enough cold night, insulated static water still freezes. Heat tracing alone on bare pipe wastes most of its output to the air and may still fail to hold the pipe above zero in wind. Together, a modest tracing wattage under correctly specified insulation will hold a static outdoor line above freezing indefinitely.
Selecting Self-Regulating Heating Cable
Self-regulating cable is the standard choice for plant freeze protection because its conductive polymer core reduces output as the pipe warms, which makes it inherently safe against overheating, allows it to be cut to length on site, and permits crossing and overlapping without hot spots. Constant-wattage cable delivers more power but must never be overlapped and requires more careful design.
| Pipe size | Recommended cable output at 10 degrees Celsius | Insulation thickness (mineral wool or equivalent) | Typical maintain temperature | Notes |
|---|---|---|---|---|
| DN15 to DN25 | 10 W per metre, single run | 25 mm | 5 degrees Celsius | Instrument tappings, drain legs, small branches |
| DN32 to DN40 | 10 to 15 W per metre, single run | 30 mm | 5 degrees Celsius | Machine branch lines, make-up water |
| DN50 | 15 W per metre, single run | 32 mm | 5 degrees Celsius | Standard branch main |
| DN65 to DN80 | 20 W per metre, single run | 40 mm | 5 degrees Celsius | Sub-headers, tower risers |
| DN100 | 20 to 30 W per metre, single or spiral run | 45 mm | 5 degrees Celsius | Main headers, yard mains |
| DN125 to DN150 | 30 W per metre, spiral or twin run | 50 mm | 5 degrees Celsius | Large mains; verify with heat loss calculation |
| Valves and flanges | Add 0.6 to 1.0 m of cable per item | Removable insulation jacket | 5 degrees Celsius | Valve bodies hold water and lose heat rapidly |
| Pump casings and strainers | Dedicated trace loop or jacket | Removable jacket | 5 degrees Celsius | Must remain serviceable without cutting insulation |
Control, Protection and Installation Discipline
Control tracing with an ambient-sensing thermostat set to energize at 5 degrees Celsius and de-energize at around 8 degrees Celsius, or with a line-sensing thermostat clamped to the pipe under the insulation for critical circuits. Ambient sensing is simpler and cheaper; line sensing is more accurate and avoids unnecessary energy use on pipes that carry warm water most of the time. Every tracing circuit must be protected by a residual current device rated at 30 mA, because moisture ingress into a damaged cable is both a fire and a shock hazard.
Installation details determine whether tracing actually works. The cable must run along the bottom quadrant of the pipe where water collects last, be fixed with glass-cloth tape rather than plastic ties that fail with age, extend under valve and flange insulation rather than stopping at them, and be terminated with proper kits at both ends. Insulation must be continuous, weather-jacketed outdoors, and sealed at penetrations. A 200 mm gap in the vapor barrier where a support bracket passes through is enough to create a cold bridge that freezes the pipe at that exact point.
Test the whole tracing system before the season, not during it. An insulation-resistance test on each circuit, a functional test of every thermostat, and a thermal check with a hand-held infrared thermometer after energizing will find the failures while there is still time to repair them. Add tracing circuit status to the plant’s alarm system where the consequences of a silent failure are high, such as on a buried yard main or a rooftop closed tower coil.
Cooling Tower Winter Operation
An open cooling tower is an evaporative device deliberately designed to expose water to cold air, which makes it the hardest component in the plant to winterize and the one that fails most spectacularly. Winter tower operation is a control problem: the tower must reject enough heat to keep hydraulic oil and condensers within range, but not so much that the return water approaches freezing and turns the fill into an ice block. The tools available are fan control, bypass control, basin heating and water level management.
Fan Control Strategy
Fan control is the primary lever because it directly sets the approach to wet-bulb temperature. In winter the heat load is often a fraction of the summer load while the ambient driving force is far greater, so a fan running at full speed will overcool the return water within minutes. A variable frequency drive on the fan motor, controlled from return water temperature rather than a fixed schedule, is the single most valuable winter modification to a tower. Where a drive is not fitted, two-speed motors, fan cycling and — as a last resort — reverse fan operation to melt accumulated ice can be used, though cycling causes more ice formation than modulation because the fill goes through repeated wet-cold-wet transitions.
Bypass and Flow Management
A tower bypass valve routes part or all of the return flow directly back to the sump without passing over the fill, holding system temperature up while keeping the pump running. Two arrangements exist. A sump bypass returns water into the basin, which keeps the basin warm and stirred but still allows the distribution system to drain — this is the preferred arrangement for cold climates. An in-line bypass diverts flow around the tower entirely, which protects the fill but leaves the tower piping static and therefore requires that the tower side be drained or traced.
Whichever arrangement is used, minimum flow over any wetted fill must be maintained. Partially wetted fill freezes faster than either fully wetted or fully dry fill, because a thin film of water on a cold surface in moving air is the ideal ice-forming condition. If the tower must operate at very low load, it is better to run one cell fully loaded and take the other cells out of service and drain them than to run all cells at low flow.
Basin Heating and Water Level
An electric immersion heater in the basin, controlled by a thermostat set to maintain around 5 degrees Celsius with a low-level cut-out, is standard practice for towers that must stay in service through the winter. The alternative and generally superior arrangement is an indoor remote sump: the tower basin drains continuously by gravity into a tank inside the heated building, so the outdoor basin is never holding a static volume of water. This eliminates the basin freeze risk entirely and is worth the capital cost in any plant that experiences sustained sub-zero conditions.
| Ambient temperature band | Fan operation | Bypass position | Basin heater | Additional actions |
|---|---|---|---|---|
| Above 15 degrees Celsius | Normal modulation on return temperature | Closed | Off | Standard water treatment and blowdown |
| 5 to 15 degrees Celsius | Drive reduced, upper speed limit applied | Modulating to hold return above 24 degrees Celsius | Standby, thermostat armed | Verify make-up line tracing energized |
| 0 to 5 degrees Celsius | Low speed or cycling; monitor for ice on louvres | Modulating, significant bypass fraction | On, maintaining 5 degrees Celsius | Increase inspection to twice per shift |
| Minus 10 to 0 degrees Celsius | Minimum speed; shut down individual cells as load falls | Large bypass fraction, sump return preferred | On, continuous | Drain out-of-service cells; check distribution laterals |
| Below minus 10 degrees Celsius | Fans off unless load demands; use bypass for control | Full bypass to sump | On, continuous with alarm | Consider full changeover to closed-loop or dry cooling |
| Shutdown of more than 48 hours | Fans off and isolated | Isolated | Off after drain | Full drain of basin, laterals, riser and pump casings |
Two inspection habits prevent most tower incidents. First, walk the tower during cold weather and look at the air inlet louvres and the outer edges of the fill: ice always forms there first, and a ring of ice on the louvres is the warning that the fill is icing internally. Second, watch the make-up water consumption trend. A sudden rise means a cracked lateral, a split coil or a burst riser, and finding it while the plant is running is far cheaper than finding it on Monday morning.
Chiller Winter Protection
The chiller is the highest-value single item in a plastics plant cooling system and its evaporator is the component least tolerant of freezing. A frozen evaporator does not simply stop working — the expanding ice deforms the tube bundle or the plate pack, opens the refrigerant circuit to the water circuit, and turns a repairable machine into a replacement. The protection strategy is layered: chemical protection through glycol, instrumented protection through interlocks, and operational protection through flow management.
Layer One: Instrumented Protection
Every chiller should have three independent protections against evaporator freezing, and all three should be tested before winter rather than assumed functional.
- Flow switch or differential pressure switch on the evaporator water circuit, hard-wired to stop the compressor. A flow switch that has been strapped, bypassed or jammed by scale is one of the most common causes of catastrophic evaporator damage. Test it by closing the isolation valve slowly and confirming the compressor stops.
- Low leaving-water-temperature cut-out, typically set at 3 degrees Celsius for a plain water system and lowered appropriately for a glycol system according to the machine’s glycol mode setting. This is a control-level protection and should trip before any mechanical damage occurs.
- Low refrigerant suction pressure cut-out, which catches the condition where the water is still flowing but the refrigerant side has gone low enough to freeze the water film at the tube wall.
On machines with a glycol mode or low-temperature application setting, that setting must be enabled and the concentration entered correctly. Running a glycol-charged machine in plain-water mode will cause nuisance low-temperature trips; running a water-filled machine in glycol mode disables the protection that would have saved the evaporator.
Layer Two: Air-Cooled Chiller Specifics
Air-cooled chillers sit outdoors and carry water inside them, which is the worst possible combination. Protection requires glycol in the chilled water loop as the primary measure, supplemented by evaporator and pipework heat tracing energized whenever the unit is off, casing panel heaters where fitted, and a pump that continues running during standby. Many machines include an anti-freeze pump-run function that starts the evaporator pump automatically when ambient falls below a set point; this function must be verified as enabled and the unit must be left with control power on all winter. Isolating a chiller’s main breaker for the winter to save standby power is a common and very expensive mistake, because it disables every one of those protections at once.
Layer Three: Operational Discipline
| Protection measure | Typical setting or practice | Verification method | Consequence if omitted |
|---|---|---|---|
| Evaporator flow switch interlock | Hard-wired compressor stop | Slowly close isolation valve, confirm trip | Evaporator freeze-up, refrigerant to water cross-leak |
| Low leaving water temperature cut-out | 3 degrees Celsius for plain water duty | Simulate with controller test function | Ice formation at tube wall |
| Glycol mode enabled with correct concentration | Set to actual charged percentage | Compare controller setting with refractometer reading | False trips or disabled protection |
| Chilled water pump run during standby | Run 10 minutes every hour minimum | Check run-hour log and timer settings | Static water in evaporator freezes |
| Evaporator and pipework heat tracing | Energized below 5 degrees Celsius ambient | Infrared check after energizing | Localized freeze at coldest section |
| Control power maintained all winter | Main breaker left closed, control on | Panel indication check on shutdown walk-round | All automatic protections disabled |
| Strainer cleaned before winter | Clean and refit, verify differential pressure | Pressure drop across strainer within design | Low flow triggers freezing at low load |
| Buffer tank insulated and traced | Insulated, traced if outdoors | Surface temperature check | Tank ice damages internals and level probes |
Where a plant genuinely shuts down for an extended period and cannot maintain control power, the chiller must be fully drained by a qualified technician following the manufacturer’s procedure, including the evaporator, condenser water side where applicable, buffer tank, pump and interconnecting pipework, with compressed air purging and drain plugs left open. Partial drainage of a chiller is worse than no drainage, because the residual water concentrates in the lowest passages of the evaporator.
Flow and Velocity: The Cheapest Anti-Freeze
Moving water is remarkably resistant to freezing. Turbulent flow continuously mixes the warmer bulk fluid with the cold boundary layer at the pipe wall, prevents the formation of a stable ice nucleus, and carries heat from the interior of the building out to the exposed sections. A pipe carrying 0.8 metres per second of 20 degree Celsius water will survive a night that solidifies the identical pipe standing static. Flow management therefore delivers more freeze protection per unit of expenditure than any other measure, and it costs nothing but pump energy.
Target Velocities
Maintain at least 0.6 metres per second in any pipe with outdoor or unheated exposure. Below roughly 0.3 metres per second the flow becomes laminar in smaller sizes, the boundary layer stabilizes, and the anti-freeze benefit largely disappears. Above 2.5 to 3.0 metres per second, erosion-corrosion becomes a concern in copper and thin-wall stainless, and noise becomes objectionable, so the practical working window for cooling distribution is roughly 0.6 to 2.5 metres per second. Note that this velocity target is also the range that keeps suspended solids in suspension and discourages biofilm attachment, so it serves water quality objectives at the same time.
| Pipe size | Flow for 0.6 m per second | Flow for 1.5 m per second | Freeze resistance at 0.6 m per second |
|---|---|---|---|
| DN25 | Approximately 1.1 cubic metres per hour | Approximately 2.7 cubic metres per hour | Adequate indoors, marginal outdoors in wind |
| DN40 | Approximately 2.7 cubic metres per hour | Approximately 6.8 cubic metres per hour | Good with insulation |
| DN50 | Approximately 4.2 cubic metres per hour | Approximately 10.6 cubic metres per hour | Good with insulation |
| DN80 | Approximately 10.9 cubic metres per hour | Approximately 27 cubic metres per hour | Strong; thermal mass assists |
| DN100 | Approximately 17 cubic metres per hour | Approximately 42 cubic metres per hour | Strong |
| DN150 | Approximately 38 cubic metres per hour | Approximately 95 cubic metres per hour | Very strong; freezing only after prolonged stagnation |
Shutdown Circulation Schedules
The critical period is not production; it is the shutdown. A simple time-clock or PLC routine that runs each circulation pump for 10 minutes at the top of every hour will keep an insulated system liquid through most cold nights, and the energy consumed over a weekend is negligible against the risk avoided. For severe conditions, switch from intermittent to continuous low-speed circulation using the pump’s variable frequency drive at 30 to 40 percent speed, which uses only a small fraction of full-load power because pump power varies approximately with the cube of speed.
Add a temperature-triggered override: if any monitored point falls below 4 degrees Celsius, the pump runs continuously regardless of the schedule and an alarm is raised. Place the temperature sensor at the coldest identified point of the circuit — usually an outdoor riser or the far end of a yard main — not in the warm plant room where it will never see the real condition.
Eliminating Dead Legs
A dead leg is any section of pipe through which water does not flow: a capped branch left from a machine that was removed, an isolated spur to a standby pump, an oversized strainer bypass, a redundant instrument tapping, a mold station that has been disconnected. Dead legs are freeze initiation sites and biofilm reservoirs at the same time. The systematic fix is to survey the plant with the circuit drawings, identify every branch that is not in active service, and either cut it back to the main and cap it flush, or bring it into circulation with a small balancing bypass. Any dead leg longer than about six pipe diameters should be treated as a defect. Plants that have gone through this exercise typically find between fifteen and forty dead legs, which is also why their water quality improves noticeably afterwards.
Water Quality Beyond Freezing
Winter is the natural time to address water quality, because the cooling load is low and circuits can be taken out of service for cleaning without hurting output. It is also the time when neglected water quality causes the most damage, because a fouled circuit has less flow, less flow means less freeze resistance, and a partially blocked mold channel is both a cooling problem and a freeze risk. The three mechanisms to manage are scale, corrosion and biofilm.
Scale: The Silent Cycle-Time Thief
Calcium carbonate scale has a thermal conductivity roughly two orders of magnitude lower than steel. A deposit of only 0.5 mm on the water side of a mold cooling channel typically reduces heat transfer efficiency by 20 to 30 percent, and the effect compounds because the reduced cross-section also cuts flow. In practice the operator sees a longer cooling phase, a hotter part at ejection, more warpage and post-shrinkage on thick sections, and a cycle time that has crept up by several percent without any process change. On extrusion lines the same deposit inside a calibration sleeve or a chill roll produces uneven surface temperature and thickness variation across the web.
| Scale thickness on water side | Approximate heat transfer loss | Typical process symptom | Recommended response |
|---|---|---|---|
| 0.1 mm | 4 to 8 percent | Barely detectable, slight cycle drift | Maintain treatment program |
| 0.3 mm | 12 to 20 percent | Cycle time creep, higher ejection temperature | Review hardness and cycles of concentration |
| 0.5 mm | 20 to 30 percent | Warpage on thick sections, output loss | Chemical cleaning of affected circuits |
| 1.0 mm | 35 to 45 percent | Significant capacity loss, quality rejects | Full descaling plus water treatment overhaul |
| Above 1.5 mm with partial blockage | Above 50 percent, flow starved | Localized hot spots, unstable process | Mechanical cleaning or channel replacement |
Control Measures
Softened make-up water is the foundation for open tower systems, and demineralized water is the correct choice for closed glycol loops where every dissolved solid stays in the system forever. Control cycles of concentration on the tower through automatic conductivity-based blowdown rather than a fixed bleed rate; running too many cycles saves water and creates scale, running too few wastes water and chemicals. A side-stream filtration loop taking 3 to 5 percent of the circulating flow through a bag, cartridge or centrifugal separator removes the suspended solids that would otherwise settle in low-velocity sections and provide a substrate for biofilm.
Biological control matters more than most plastics plants assume. An open tower is an excellent bacterial incubator, and biofilm is an even better insulator than scale — a biofilm layer produces roughly the same thermal resistance as a scale layer several times thicker. It also drives microbiologically influenced corrosion under the deposit. Use a program that alternates between two non-oxidizing biocides on a rotating schedule to prevent resistant populations from establishing, and combine periodic dosing with a dispersant that lifts existing film off the surfaces so the biocide can reach the organisms underneath.
Winter Cleaning Window
Plan the annual cleaning during the low-load period. Take one circuit at a time out of service, circulate an appropriate descaling solution at the temperature and duration specified by the chemical supplier, neutralize, flush thoroughly, then passivate and recharge with treated water or pre-mixed glycol at the design concentration. Record before-and-after flow readings on each mold circuit: a mold that shows a 30 percent flow improvement after cleaning was silently costing cycle time all year. Inspect and clean all strainers, replace side-stream filter elements, and verify that every flow indicator and thermometer on the distribution manifolds still reads correctly, because instrumentation that has failed unnoticed is the reason fouling goes undetected for years.
Equipment-Specific Winter Checklist by Machine Type
Generic winterization advice fails because every machine family has its own critical water circuit and its own characteristic freeze failure. An extrusion blow molding machine loses molds; a PET stretch blow molding machine loses preform oven cooling and mold base circuits; a twin-screw pelletizing line loses the die face water ring and the strand bath; a pipe line loses the vacuum calibration tank; a sheet line loses chill rolls; a recycling washing line loses everything, because it is essentially a building full of water tanks. The table below is the operational core of this guide and should be transcribed directly into the plant’s winter maintenance schedule.
| Machine type | Critical water circuit | Freeze risk | Protection method | Restart check |
|---|---|---|---|---|
| Extrusion blow molding machine | Mold cooling channels, blow pin and neck cooling, hydraulic oil cooler, die head cooling collar | Very High — deep drilled mold channels cannot gravity drain | Purge each mold circuit individually at 0.4 to 0.6 MPa, or keep 30 percent glycol circulating; disconnect and drain all hoses | Flow check on every mold circuit; inspect parting line area for weeping; verify oil cooler outlet temperature stable |
| PET stretch blow molding machine | Preform oven and lamp housing cooling, mold body and base mold cooling, high-pressure air compressor aftercooler | High — many small-bore circuits and manifold blocks | Glycol at 30 percent on the chiller loop; purge base mold circuits; drain compressor aftercooler and receiver | Confirm oven cooling flow before lamps energize; check base clearance forming on first bottles; drain receiver condensate |
| Injection blow molding machine | Injection mold and core rod cooling, blow station cooling, hydraulic oil cooler, feed throat jacket | High — core rod circuits are narrow and hold water | Individual circuit purge; leave couplings disconnected on long shutdowns; glycol on the chiller loop | Verify core rod temperature uniformity; check for water in the clamp area; confirm feed throat cooling flow |
| Twin-screw compounding and pelletizing line | Barrel feed zone jacket, screw core cooling, die face water ring or underwater cutting loop, strand bath, gearbox oil cooler | High — the pelletizing water loop is the most exposed | Drain strand bath and water ring loop completely; purge barrel jackets; glycol on the process water loop where the tank is near an outside wall | Barrel jacket flow verified before heating; water ring pressure and flow stable; strand bath level and overflow correct |
| Pipe extrusion line vacuum calibration tank | Vacuum tank, spray nozzle headers, calibration sleeve cooling, vacuum pump seal water | Very High — large open tank volume, pump seal water freezes first | Full tank drain, nozzle header purge, vacuum pump seal water line drained and traced | Nozzle spray pattern check on every header; vacuum level holds at set point; sleeve cooling flow balanced |
| Sheet and board extrusion chill roll stack | Chill roll internal passages, rotary unions, roll temperature controller loop | High — a cracked roll shell is a Very High loss | Purge each roll through the low port; never leave a roll static and full outdoors of the heated zone; glycol on the roll temperature loop | Rotate rolls slowly while warming; check rotary union for leakage; verify surface temperature uniformity across the face |
| Recycling washing line | Wash tanks, friction washer sprays, float wash tanks, dewatering machine, hot wash tank, water treatment and recirculation | Very High — the highest water inventory in any plastics plant | Drain every tank and transfer pump; purge spray headers; trace and insulate all outdoor transfer lines and the treatment plant | Fill tanks in sequence and check for leaks at every seam; verify pump seals; confirm spray nozzle coverage |
| Film extrusion and casting line | Casting roll cooling, air knife and edge trim cooling, water bath where used | High | Purge roll circuits, drain bath and pump casings, trace outdoor supply | Roll surface temperature profile check; thickness uniformity on first roll produced |
| Auxiliary equipment: chillers, towers, mold temperature controllers, dryers | Evaporator, tower basin, controller heating and cooling loops, dryer aftercoolers | Very High for outdoor items | Glycol plus instrumented protection on chillers; basin heater or remote sump on towers; drain controllers not in service | Full protection interlock test before returning to service; verify glycol concentration by refractometer |
Two operational habits multiply the value of this table. First, assign a named owner to each machine’s winterization, not to the maintenance department as a whole, and require a signature. Second, run the checklist as a dry-run in late autumn while the weather is still mild, so that missing drain valves, seized cocks, lost pump plugs and unmarked circuits are discovered under comfortable conditions rather than at midnight in a cold snap.
Safe Restart After Cold Shutdown
More equipment is damaged during restart than during the freeze itself. A plant that has survived a cold period intact can still destroy a mold by admitting cold water into hot steel, crack a chill roll through thermal shock, wreck a pump by starting it dry, or flood a workshop by pressurizing a circuit that has an unnoticed crack. The restart sequence below is deliberately slower than the one most plants use, and the extra time is repaid many times over.
Step 1: Visual and Physical Inspection Before Any Water
Walk every circuit before opening a single valve. Look for bulged pipe sections, split fittings, deformed valve bodies, distorted plate heat exchanger frames, cracked pump casings, and any component showing frost damage to insulation or paintwork. Check that all drain plugs removed during winterization have been refitted with new seals and that all drain valves are closed. Confirm that pump shafts turn freely by hand. Check that every hose and quick coupling has been reconnected to the correct circuit — reversed supply and return on a mold circuit is a classic post-shutdown error that produces mysterious cooling problems for days.
Step 2: Slow Fill With Systematic Venting
Fill from the lowest point upward at a restricted rate, with every high-point vent open. Rapid filling traps air pockets that later cause flow starvation, cavitation and localized overheating. On a large system, plan the fill to take at least thirty minutes rather than a few minutes at full make-up flow. Walk the system as it fills and close each vent as clean water appears. Where the system is glycol-charged, fill with pre-mixed fluid at the design concentration; do not fill with water and then attempt to add glycol.
Step 3: Staged Warm-Up to Avoid Thermal Shock
Never introduce cold water into hot equipment or hot water into cold equipment. If molds, rolls or barrels are already at temperature, establish water flow first and then raise temperature progressively, or bring the water up in stages of no more than 10 to 15 degrees Celsius with a hold at each stage. Thermal shock is what turns a hairline freeze crack that would have held into a full through-wall failure, and it is what cracks chill roll shells and hard-chromed surfaces. On sheet and board lines, rotate the rolls slowly during warm-up so the shell heats evenly around its circumference rather than only on the water-contact side.
Step 4: Pressure Test Before Production
Hold the circuit at 0.6 MPa for 30 minutes with the make-up isolated and watch the gauge. A pressure decay indicates a leak somewhere, and finding it now is far cheaper than finding it when a mold has been mounted and the line is producing. On systems with a lower design pressure, test at the design working pressure rather than 0.6 MPa. Record the start pressure, end pressure and ambient temperature, because a small decay caused purely by cooling of the test fluid can be mistaken for a leak.
Step 5: Commission Machine by Machine and Record
| Restart step | Action | Acceptance criterion | Record |
|---|---|---|---|
| 1. Visual inspection | Walk all circuits, check for damage and reinstated plugs | No deformation, no missing plugs, shafts turn freely | Signed inspection sheet with defects listed |
| 2. Slow fill and vent | Fill from low point, vent all high points | Clean water at every vent, no air noise in pipework | Fill start and finish time, make-up volume |
| 3. Pump start and flow balance | Start pumps individually, check suction pressure | Stable suction pressure, no cavitation noise, design flow at each branch | Flow and pressure at each manifold |
| 4. Staged warm-up | Raise temperature in 10 to 15 degree Celsius steps | No leakage at any stage, uniform surface temperature | Temperature ramp log |
| 5. Pressure hold test | 0.6 MPa for 30 minutes with make-up isolated | No measurable decay allowing for temperature change | Start and end pressure, ambient temperature |
| 6. Protection interlock test | Test flow switches, low temperature cut-outs, alarms | Each protection trips on demand | Interlock test certificate |
| 7. Fluid verification | Refractometer and pH check on glycol loops | Concentration within 3 percentage points of design, pH 8.0 to 9.5 | Water analysis sheet |
| 8. Machine-by-machine commissioning | Return one machine at a time to production | Cycle time and product quality match pre-shutdown baseline | First-article inspection and cycle log |
The final discipline is trend comparison. Compare cycle time, cooling water differential temperature and machine energy consumption against the pre-shutdown baseline for the first week of operation. A circuit that is 10 percent down on flow because of a partially blocked channel or an air pocket will show up in that comparison long before it shows up as a quality problem.
Requirement to Recommended Winterization Package
Winterization is not one solution but a package assembled from the measures above, matched to climate, shutdown pattern and product requirements. The table below maps common plant scenarios to a recommended package. Treat it as a starting specification to be refined against the plant’s own recorded minimum temperatures and shutdown calendar.
| Plant scenario | Recommended glycol strategy | Heat tracing and insulation | Drainage policy | Circulation policy | Additional measures |
|---|---|---|---|---|---|
| Severe cold region with outdoor chillers and rooftop towers | Inhibited MEG at 40 to 50 percent on all outdoor and closed loops | Full tracing on all outdoor pipe, valves, pumps and tower make-up; 40 to 50 mm insulation with weather jacket | Drain only for shutdowns longer than two weeks | Continuous low-speed circulation via drive at 30 to 40 percent | Indoor remote sump, basin heaters, traced instrument tappings, temperature alarm at coldest point |
| Cold-humid region with occasional hard frost | Inhibited MEG at 25 to 30 percent on chiller and outdoor loops | Tracing on outdoor small bore and valves; 30 to 40 mm insulation | Drain seasonal and idle circuits only | Intermittent pump run, 10 minutes every hour below 5 degrees Celsius | Dehumidification control in plant room, condensation management on chilled lines |
| Weekend or intermittent shutdown, restart every Monday | MEG at 30 percent — drainage is impractical at this frequency | Tracing on all exposed sections; insulation continuous | No routine weekend drainage | Timer-based circulation through the whole shutdown with low-temperature override | Automatic Friday shutdown routine in the PLC; alarm to on-call phone |
| Continuous 24-hour operation, no planned shutdown | MEG at 25 to 30 percent as insurance against unplanned stops | Tracing on outdoor sections and dead-end branches | Drain only for planned annual maintenance | Process flow provides protection; standby pump auto-start on flow loss | Power failure contingency plan, generator-backed circulation pump |
| Food-grade or pharmaceutical container production | Food-safe PG at 30 to 40 percent on all product-adjacent circuits; MEG permitted only on fully segregated utility loops | Standard tracing and insulation; hygienic jacketing where required | Drain and sanitize together during planned stops | Continuous circulation to prevent stagnation and biofilm | Documented fluid traceability, segregated fill points, leak-detection on exchangers |
| Mild winter region, brief overnight frost only | Glycol optional; 20 percent MEG on outdoor chiller loops as low-cost insurance | Insulation on outdoor pipe, tracing only on small-bore and valves | Drain idle equipment and seasonal lines | Overnight timer circulation on frost forecast | Frost-forecast trigger procedure and a documented cold-snap response plan |
| New plant under design | Design the loop for glycol from the start with pumps and exchangers sized for the derated fluid | Tracing and insulation specified as part of the piping package | Design every circuit to be fully drainable with numbered low points | Variable frequency drives on all circulation pumps as standard | Indoor sump, buried lines below frost line, no dead legs, monitoring points designed in |
Wanplas Group Equipment and Winterization Support
Wanplas builds machines for customers in more than 100 regions, including many with severe winters, so cooling circuit design and winter serviceability are treated as engineering requirements rather than afterthoughts. Across the group’s seven specialized factories, every machine family has its own cooling architecture and its own critical winter points, and the group’s engineers document those points for each delivered line.
Cooling Circuit Priorities by Wanplas Factory
| Wanplas factory | Machine category | Critical cooling circuit in winter | Design feature that aids winterization |
|---|---|---|---|
| Apollo | Extrusion blow molding machines, 200ML to 1500L | Mold cooling channels, die head collar, hydraulic oil cooler | Manifold-based mold water distribution with individual circuit isolation and drain points |
| Kerke | Twin-screw compounding extruders and pelletizing systems | Barrel feed zone jacket, screw core cooling, die face and strand bath water | Segmented barrel jackets with independent low-point drains on each zone |
| YuDa | PET bottle blow molding machines | Oven and lamp cooling, mold body and base mold circuits | Modular design allows each cooling module to be isolated and purged separately |
| Aibim | Injection blow molding machines, 3ML to 1000ML | Core rod and injection mold cooling, blow station, hydraulic oil cooler | Accessible manifold layout in the enlarged mold setting space simplifies purging |
| Polyretec | Washing lines and pelletizing lines | Wash tanks, friction washers, dewatering, transfer and treatment lines | Tank drains sized for rapid emptying; pump casings with accessible drain plugs |
| Faygo | Pipe and profile extrusion lines | Vacuum calibration tank, spray headers, sizing sleeve cooling | Tank low-point drains and header isolation valves included in the standard line |
| YuanSu | Film, sheet and board extrusion lines | Chill roll internal passages, casting roll, roll temperature control loop | Roll circuits ported for full drainage; rotary unions accessible for service |
Product Focus: Apollo Extrusion Blow Molding Machines
Apollo, a Wanplas factory in Zhangjiagang near Shanghai, has more than 20 years of extrusion blow molding experience, an 8,000 square metre factory, and over 4,000 machines running in more than 90 countries across ten series and more than eighty models. For plants in cold climates the choice between hydraulic and fully electric machines has a direct winter consequence: a fully electric machine has no hydraulic oil cooling loop at all, which removes one entire water circuit from the winterization scope.
| Series | Container range | Typical materials | Cooling circuits requiring winter protection | Best suited to |
|---|---|---|---|---|
| ABLB series | 200ML to 20L, eight machine types | PE, PP, PVC, PA, PC, ABS, PS, EVA, TPU, PETG | Mold cooling, blow pin cooling, die head collar, hydraulic oil cooler | General packaging containers, daily chemical and food bottles |
| ABLB 55 | 2L to 3L | PE, PP and blends | Mold cooling, blow pin cooling, hydraulic oil cooler | Dedicated medium-volume container production |
| ABLD series | 20L to 1500L, three machine types | PE, PP | Large mold cooling circuits, accumulator head cooling, hydraulic oil cooler | Drums, tanks, large industrial containers |
| Fully Electric series | 200ML to 20L | PE, PP, PVC, PC, PETG | Mold cooling and die head only — no hydraulic oil circuit | Cold-climate plants and sites with high environmental requirements |
Product Focus: Kerke Twin-Screw Compounding Extruders
Kerke, a Wanplas factory with more than 12 years of dedicated experience, a factory area approaching 20,000 square metres and over 2,000 machines running in more than 70 countries, builds the KTE series of parallel co-rotating twin-screw extruders from the laboratory-scale KTE-16B up to the high-output KTE-135D. Compounding lines concentrate several winter-critical water circuits in one place: the feed zone jacket that must stay cool to prevent bridging, the screw core cooling that stabilizes melt temperature, and the pelletizing water loop that is usually the coldest and most exposed part of the line.
| Model range | Indicative output | Typical L/D configuration | Winter-critical water points | Typical application |
|---|---|---|---|---|
| KTE-16B laboratory extruder | From approximately 30 kg per hour | Configurable, commonly 40:1 to 48:1 | Feed throat jacket, small strand bath | Formula trials, R and D, small batch compounds |
| KTE mid-range models | Several hundred kg per hour | Configurable barrel and screw arrangement | Segmented barrel jackets, screw core cooling, strand bath | Color masterbatch, filler masterbatch, additive masterbatch |
| KTE-135D | High-capacity production duty | Configurable, optimized for throughput | All barrel zones, screw core, die face water ring or underwater pelletizing loop | Engineering plastic compounds, cable compounding, WPC composites |
| SE series single-screw extruder | 30 kg per hour to 800 kg per hour | Standard recycling configuration | Feed zone jacket, strand bath, melt filtration cooling | Plastic recycling and regrind pelletizing |
| Double-stage extrusion system | Per configuration | Mother-baby arrangement | Both stage feed zones, interconnecting melt path cooling | Heat-sensitive and special materials |
Applications and End Products
The winterization measures in this guide apply across the industries Wanplas equipment serves: food and beverage packaging, where PET bottles, HDPE containers and food-grade recycled flakes demand consistent mold temperature; daily chemical products, where wall thickness distribution on shampoo and detergent bottles is directly governed by cooling stability; medical and pharmaceutical containers, where propylene glycol is the mandatory freeze protection chemistry on product-adjacent circuits; building materials, where PVC and PE pipe lines depend on vacuum calibration tank temperature for dimensional accuracy; chemical industry containers and drums produced on large accumulator-head machines; masterbatch and compound production, where die face water temperature governs pellet shape; and plastic recycling, where a washing line’s water inventory is both the process medium and the largest freeze liability on the site.
Requirement to Recommended Wanplas Equipment
| Customer requirement | Recommended Wanplas equipment | Cooling water consideration in cold climates |
|---|---|---|
| 200ML to 20L packaging containers, cold-climate site, minimum water circuits | Apollo Fully Electric extrusion blow molding series | No hydraulic oil cooling loop; only mold and die head circuits need winter protection |
| 2L to 3L containers, steady volume production | Apollo ABLB 55 | Individual mold circuit isolation for fast purging at shutdown |
| 20L to 1500L drums and industrial tanks | Apollo ABLD series | Large mold water volume — glycol strongly preferred over drainage |
| Masterbatch or compound production up to high capacity | Kerke KTE series, up to KTE-135D with matched pelletizing system | Segment barrel jackets and pelletizing loop separately; pelletizing water is the exposed circuit |
| Laboratory formula development | Kerke KTE-16B laboratory twin-screw extruder | Small water volume; full drainage is practical between campaigns |
| 8,000 to 15,000 bottles per hour PET production | YuDa FGX high-speed PET bottle blow molding series | Oven and mold base circuits are small bore; glycol plus circulation recommended |
| Lower-volume PET bottle production, limited budget | YuDa standard-speed full automatic or semi-auto series | Fewer circuits; drainage practical for seasonal shutdown |
| 3ML to 1000ML pharmaceutical and cosmetic containers | Aibim IBM75, IBM65 or IBM55 Hybrid injection blow molding machines | Core rod circuits require individual purging; food-safe PG where product contact risk exists |
| Food-grade PET flake production, 500 kg per hour to 6000 kg per hour | Polyretec food grade PET crushing and washing line | Highest water inventory on site; full tank drainage plus traced transfer lines |
| PP and PE film and woven bag recycling, 500 kg per hour to 1500 kg per hour | Polyretec soft plastic crushing and washing line with one-step pelletizing option | Drain wash tanks and dewatering machine; trace outdoor treatment lines |
| PVC, PE or PP-R pipe production, 12 mm to 575 mm | Faygo pipe extrusion lines, including PVC, PVC-O, PP-R and PE-RT lines | Vacuum calibration tank and spray headers are the critical freeze points |
| Film 0.008 mm to 0.25 mm, sheet 0.25 mm to 2 mm, board 3 mm to 50 mm | YuanSu film, sheet and board extrusion lines | Chill roll passages must be purged; glycol on the roll temperature loop |
| Complete new plant including utilities design | Wanplas turnkey project scope with factory layout and utility planning | Cooling circuits designed drainable from the outset, with glycol-rated pumps and exchangers |
Winterization Documentation and Remote Guidance
For every delivered line Wanplas can supply English-language cooling circuit diagrams that identify each circuit, its design flow and temperature, and every low-point drain and high-point vent. On request the group’s engineers prepare a plant-specific winter maintenance standard operating procedure covering the drain-down sequence, glycol concentration recommendation for the customer’s recorded climate, heat tracing scope and the restart checklist. Remote guidance is available through video walk-throughs of the drainage and purging procedure and review of the customer’s completed checklists before a shutdown, which is often the difference between a documented winterization and an assumed one.
Service and Support
Winter reliability depends as much on the supplier relationship as on the hardware. Wanplas applies a consistent set of service commitments across all seven of its factories, and each one has a direct bearing on how a plant survives a cold season.
Testing Before Shipment
Every machine is run and inspected at the factory before dispatch, and on pipe and profile extrusion lines the standard includes a 72-hour continuous operation test. Cooling circuits are pressure tested and flow balanced during that test, so the line arrives with a known-good water system and documented baseline flow figures. Those baseline figures matter in winter: when a circuit is refilled after a shutdown and the flow reads 20 percent below the factory test value, the plant knows immediately that something is blocked or air-locked rather than guessing.
Installation, Commissioning and Training
Wanplas engineers attend site for installation and commissioning, and the commissioning scope includes handing over the cooling circuit layout with the drain and vent schedule. Operator and maintenance training covers the drain-down sequence, the compressed air purge procedure at 0.4 to 0.6 MPa, glycol concentration checking with a refractometer and the staged restart procedure. Where the customer is building a new plant, the group also provides water and electricity design support, factory site layout including 3D workshop design, and worker configuration and training, so that cooling distribution is laid out to be drainable and traceable before the concrete is poured.
Spare Parts and Warranty
The group’s shared policy provides USD 500 free parts per year, with free replacement of parts damaged within the warranty period. For winterization the parts most worth holding on site are the small, unglamorous items that stop a restart: drain valves and plugs, quick coupling seals, hose assemblies, flow switches, thermostats for heat tracing circuits, and refractometer and pH test consumables. Wanplas can supply a recommended cold-climate spares list matched to the delivered machine list.
Remote Support and Monitoring
Remote technical support is available for troubleshooting during and after a cold snap, including review of controller data where the machine supports remote monitoring. On PET blow molding equipment the remote monitoring capability allows engineers at the China headquarters to review PLC data and feed abnormality warnings back to the customer site, which is particularly useful for catching a cooling flow deviation before it becomes a quality problem.
Open Factory Policy
Wanplas operates an open factory policy across the group and welcomes customer visits to any of the seven factories. Customers planning a cold-climate installation are encouraged to visit during machine testing, walk the cooling circuit layout with the engineering team, and agree the winterization scope before shipment rather than after the first frost.
Frequently Asked Questions
What glycol concentration do I actually need for a plastics plant?
Set the concentration from the lowest recorded ambient temperature at the most exposed point of the circuit, then add a margin of about 5 degrees Celsius. In most temperate regions 25 to 30 percent volume ethylene glycol is sufficient. Severe cold regions with outdoor chillers, rooftop towers and yard mains normally require 40 to 50 percent. Going above 60 percent is counterproductive because the freeze point curve inverts and viscosity becomes unmanageable.
Is draining the system safer than adding glycol?
Draining is safer only when it is complete and verified. Gravity drainage alone always leaves residual water in mold cooling channels, plate heat exchanger ports, pump volutes and looped hoses, and that residual water is exactly what cracks components. Drainage must be followed by compressed air purging at 0.4 to 0.6 MPa with a positive verification at each outlet. For plants that shut down every weekend, glycol plus circulation is far more reliable than repeating a drainage procedure fifty times a year.
How much cooling capacity do I lose after adding glycol?
A 30 percent volume ethylene glycol mixture reduces specific heat by roughly 9 to 11 percent and raises viscosity substantially at low temperature. The combined effect on plate heat exchangers, oil coolers and mold channels is typically a 10 to 25 percent reduction in heat transfer capability, and at 50 percent concentration it can approach 30 percent. Compensate with higher volumetric flow, additional exchanger area or a lower supply temperature, and re-check pump head and motor current after charging.
Can I use automotive antifreeze in a plastics plant cooling system?
No. Automotive coolant inhibitor packages are formulated for closed engine loops containing aluminum and cast iron, not for industrial systems that combine copper mold channels, stainless plate packs, galvanized distribution pipe, bronze pump internals and elastomer seals. Use an industrial inhibited glycol specified for process cooling duty, confirm compatibility with every metal and elastomer in the loop, and never mix inhibitor chemistries.
What flow velocity actually prevents freezing?
Maintain at least 0.6 metres per second in exposed piping. Turbulent flow continuously disrupts the cold boundary layer at the pipe wall and carries heat from the building interior out to the exposed sections. Combine this with a shutdown schedule that runs each circulation pump for at least 10 minutes every hour, and add a low-temperature override that switches to continuous circulation whenever any monitored point falls below 4 degrees Celsius.
How does scale in a mold cooling channel affect cycle time?
A scale layer of only 0.5 mm on the water side of a mold cooling channel reduces heat transfer efficiency by 20 to 30 percent, and because the deposit also narrows the passage the flow falls at the same time. The visible symptoms are a longer cooling phase, a higher part temperature at ejection, more warpage and post-shrinkage on thick sections, and a cycle time that has drifted upward without any process parameter having changed.
Do I still need heat tracing if the system is glycol-protected?
Usually yes, in selected locations. Glycol prevents the fluid from freezing solid, but as temperature falls the viscosity rises sharply and slush can form near the freeze point, starving flow and tripping flow switches. Outdoor small-bore piping, valve bodies, pump casings, instrument tappings, drain legs and cooling tower make-up lines normally justify tracing even on a glycol-protected system.
What is the safest way to restart after a hard freeze?
Inspect visually for bulged pipe, split fittings and cracked casings before admitting any water. Refill slowly from the lowest point with every high-point vent open, warm the system in stages of no more than 10 to 15 degrees Celsius to avoid thermal shock, hold a pressure test at 0.6 MPa for 30 minutes, test all protection interlocks, verify glycol concentration and pH, then return machines to production one at a time while recording flow, pressure, temperature and cycle time against the pre-shutdown baseline.
Which single measure gives the best protection for the least expenditure?
Maintaining circulation. A timer or PLC routine that keeps water moving during shutdown costs almost nothing to implement, uses very little energy, and protects every part of the circuit simultaneously. It should be the first measure implemented, with glycol, tracing and drainage layered on top according to the plant’s climate and shutdown pattern.
Conclusion
Winter anti-freezing maintenance for plastic machinery cooling water systems is an engineering program, not a checklist that gets pinned to a wall in November. It begins with mapping the three circuits that exist in every plastics plant — mold and product cooling, machine and oil cooling, and the many small process-specific circuits — and ranking every component by water temperature, exposure, thermal mass and flow condition. It continues with a deliberate choice between the three protection strategies: chemical protection through correctly specified and correctly maintained inhibited glycol, thermal protection through heat tracing under continuous insulation, and mechanical protection through verified drainage and compressed air purging. Above all it depends on keeping water moving, because circulation is the cheapest and most universally effective anti-freeze available.
The details are what separate a plant that sails through a cold snap from one that spends February repairing molds. Glycol concentration set from the coldest recorded temperature rather than the average, with the resulting 10 to 25 percent heat transfer penalty designed into the pump and exchanger sizing. Inhibitor reserve tested annually rather than assumed. Every mold circuit purged individually and signed off by name. Heat tracing tested before the season with an insulation-resistance check and an infrared scan. Cooling tower fans modulated on return water temperature with a sump bypass rather than cycled on and off. Chiller flow switches and low-temperature cut-outs proven by test rather than trusted. Dead legs found and cut out. Scale controlled so a 0.5 mm deposit is never allowed to steal 20 to 30 percent of the mold’s cooling capability. And a slow, staged restart with a pressure hold test before any mold goes back on a machine.
Wanplas designs its extrusion blow molding machines, twin-screw compounding extruders, PET bottle blow molding machines, injection blow molding machines, recycling washing and pelletizing lines, pipe and profile extrusion lines and film, sheet and board extrusion lines with cooling circuits that can be isolated, drained and purged, because equipment exported to more than 100 regions has to survive climates the factory never sees. The group backs that with factory testing before shipment, on-site installation and commissioning, operator training that covers the winterization procedure itself, USD 500 free parts per year, remote technical support and an open factory policy.
If you are planning a new line for a cold-climate site, upgrading an existing plant’s cooling infrastructure, or simply want a second opinion on whether your current winterization program would survive a hard freeze, send the Wanplas engineering team your machine list, your cooling circuit layout and your site’s recorded minimum temperatures. They will return a tailored winterization specification with a glycol concentration recommendation, a heat tracing and insulation scope, a drain-down and restart procedure written for your specific equipment, and a matched machine configuration if new capacity is part of the plan. Sample trial runs and factory visits are welcome at any of the group’s factories, and the cooling system walk-through is part of the standard visit.

